Cooling Water Chiller SUNDI -45℃~300℃
scroll left
  • Cooling Water Chiller SUNDI 45 300
scroll right

Cooling Water Chiller SUNDI -45℃~300℃

Price: US$ 3000
Minimum Order:
Payment Terms: L/C, D/A,D/P,T/T,Western Union,MoneyGram
Port of Export:
Product Details
Model No.: Brand Name: lneya
Certification:
Specification: It is important to choose the suitable heat conduction medium, to make sure that system works stably.
Packaging & Delivery
Packaging: standard wooden case
Delivery/Lead Time:
Production Capacity: 100
Product Description
It is important to choose the suitable heat conduction medium, to make sure that system works stably. To choose the suitable medium according to the working temperature of the system is essential.
How to Determine Freezing Water Flow Rate?

A lot of people will ask such a question when they buy a cold water machine -- how do you determine the freezing water flow of a refrigerated water unit? So which aspects should we consider the cold water flow?
1. Water pressure test of the unit in and out of the water pipe.
Detect the pressure value of the in- and out-water, then refer to instruction about the water flow under this circumstance and determine whether the water system is normal by looking at the description in the corresponding table or flow diagram of the unit. This difference is also used to determine which part of the water pipeline has a large resistance and make corresponding rectification plan and action.
2. The air inlet temperature of the compressor should be tested only when the refrigeration operation is carried out.
If the temperature of the refrigerated water chiller is tested lower than zero after running for 30 minutes, then water flow is not enough on water side heat exchanger which causes evaporation temperature and pressure to fall and cause freon in evaporator flow to the compressor suction duct in evaporation heat. That brings about the fact that the compressor suction temperature below zero. In addition, the evaporation pressure and evaporation temperature caused by low temperature setting should be excluded. However, the low-temperature unit can be considered normal as long as there is 6 ~ 8 ℃ overheat of compressor suction. So under normal water flow, the compressor suction temperature generally will be greater than 0 ℃. Temperature lower than this value should be ruled out water system problems.
3. The current needs to be tested when the pump runs.
By detecting the current of the pump of water industrial chiller and comparing with rated current, you can determine the actual water flow, whether its water flow is big or small. Refer to the parameters above, you can draw an exact water system testing analysis report.
Cooling Water Chiller SUNDI -45℃~300℃

SUPPLIER PROFILE
Company: Wuxi Guanya Refrigeration technology co., ltd
City/State wuxi, jiangsu Country: China  
Business Type: Export - Manufacturer / Trading Company Established: 2006
Member Since: 2019 Contact Person Tony Sen
SUPPLIER PROFILE
City/State/Country -
wuxi, jiangsu
China  
Business Type -
Export - Manufacturer / Trading Company
Established -
2006
Member Since -
2019
Contact Person -
Tony Sen